Availability:
Estimated Arrival: Between Feb 09 and Feb 16. *ETA to Continental USA Only
Shipping & Returns: Free Shipping. All The Time.

Goodman Packaged Heat Pumps 2 to 5 Tons Up to 16 SEER
The Goodman packaged heat pumps provide efficient electric heating and cooling to your home or business.
Standard Features
- High-efficient scroll compressor
- Multi-speed ECM indoor blower motor
- Copper tube/aluminum fin condenser coil
- All-Aluminum evaporator coil
- Totally enclosed, permanently lubricated condenser fan motor
- Fully charged system
- Quiet horizontal discharge
- AHRI Certified; ETL Listed
Cabinet Features
- Heavy-gauge galvanized-steel cabinet with Architectural Gray powder-paint finish
- Aluminum foil-facing internal insulation reinforced with fiberglass scrim
- Fully insulated blower compartment with convenient access panels
- Meets cabinet air leakage requirements when tested in accordance with ASHRAE standard 193
- Louvered condenser coil protection
- One footprint for all tonnages
Model: GPH1648H41
Dimensions
Dimensions | |
Width | 66" |
Depth | 34" |
Height | 35" |
Specifications
Model | GPH16H |
Type | Packaged Heat Pump |
Compressor | Single Stage |
ENERGY STAR Certified | NO |
COOLING CAPACITY
Cooling Capacity (BTU/h) | 46,000 |
Sensible BTU/h |
34,600 |
SEER / EER | 16.0 / 12.0 |
Decibels | 80 |
AHRI Numbers | 7953729 |
HEATING CAPACITY
BTU/h (47ºF) | 44,000 |
C.O.P (47ºF) | 3.8 |
BTU/h (17ºF) | 26,000 |
C.O.P (17ºF) | 2.4 |
HSPF | 8.0 |
EVAPORATOR MOTOR
Type |
ECM |
Wheel (D x W) |
10 x 8 |
Cooling CFM |
1,600 |
Fan-Only CFM | 1,400 |
RLA |
5.4 |
No. of Speeds | 5 |
Horsepower- RPM | 3/4- 1,050 |
Face Area (ft²) | 6.2 |
Rows Deep/ Fins per Inch | 4/ 14 |
Indoor Metering Device Size | TXV |
Filter Size (ft²) |
(2) 20 x 20 x 1 |
Drain Size (NPT) | 3/4" |
Refrigerant Charge (oz.) | 170 |
Horsepower- RPM | 1/4- 1,075 |
RLA/LRA |
1.4 / 2.9 |
Fan Diameter/ # Fan Blades | 22 / 4 |
Face Area (ft²) | 17 |
Outdoor Metering Device Size | TXV |
Rows Deep/ Fins per Inch | 2 / 16 |
Quantity / Type | 1 / Scroll |
Stage |
Two |
Compressor RLA/LRA |
21.2 / 104 |
Voltage-Phase (60 Hz) | 208/230-1 |
Indoor Blower FLA | 5.4 |
Outdoor Fan RLA |
1.4 |
Total Unit Amps | 28 |
Min. Circuit Ampacity | 35 |
Min. Overcurrent Protection (amps) | 50 amps |